The Danlers Wall Mounted PIR Occupancy Switch is an efficient and reliable solution for automatic lighting control in various spaces, such as small offices, meeting rooms, and tutoring rooms. This innovative occupancy switch replaces an existing wall switch and does not require a neutral wire, making installation quick and simple. The WAPIR model features a manual override off switch for added flexibility, as well as an intuitive push button for switching between override off and automatic modes. The integrated LED indicator provides visual feedback, ensuring the switch is easy to use and configure.

  • Download Product Technical Data Sheet

  • Voltage: 230V
  • Load Capacity: Switches up to 6A (1500W) for resistive, fluorescent, electronic, wire-wound transformers, LED lamps, and drivers; 1A (250W) for fans.
  • Minimum Load: 20W per WAPIR in the circuit.
  • Manual Override: Push button to toggle between override off and automatic mode.
  • LED Indicator: A short press activates override off mode; the LED pulses slowly to show the mode. LED can be deactivated with a long press of the button.
  • Mounting: Surface-mounted, fits into plaster-depth wall boxes.
  • Scan Angle: 120° detection range for wide coverage.
  • Detection Range: Up to 10 meters in diameter on the floor.
  • Optimum Mounting Height: 1.8 meters for effective operation.
  • Wiring: No neutral wire is required; must be wired to a permanent live supply.
  • Load Capacitor: Supplied to augment small loads for consistent performance.
  • Dimensions: Height: 86 mm, Width: 86 mm, Depth: 22 mm.
  • Switching Time Delay: 10 seconds for reliable detection.
  • Maximum Duty Cycle: 40 minutes.
  • Current Requirements: Minimum starting current 1A; maximum starting current 6A.

Why Choose the Danlers PIR Occupancy Switch?
This occupancy switch is a perfect choice for environments where energy efficiency and user-friendly operation are essential. With no neutral wire required and a simple installation process, it's an excellent option for retrofit projects. The WAPIR model’s manual override function, LED indicator, and adaptable settings make it a versatile addition to your lighting control system.